Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
KURSUS LATIHAN KEKOMPETENAN
Unit PerlindunganSeksyen Latihan Penghantaran
Institut Latihan Sultan Ahmad Shah (ILSAS)
PERLINDUNGAN PENGHANTARAN(SETAKAT 132kV)
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
SKIM PERLINDUNGAN ALATUBAH.
RESTRECTED EARTH FAULT(REF)
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
Institut Latihan Sultan Ahmad Shah(ILSAS)
ObjektifPada akhir pengajaran, pelatih-pelatih akan dapat 1. Mengenal pasti dan melukis litar skimatik
perlindungan geganti REF.2. Mengira tatahan perlindungan geganti REF 3. Mengaturkan prosidur pengujian skim
perlindungan geganti REF.4. Melukis litar pengujian “secondary”, “primary”
dan “stability”.dengan betul apabila skim perlindungan REF
digunakan pada alatubah.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
RESTRICTED EARTH FAULT SCHEME FOR STAR WINDING
Relay operates for earth fault within protected zone.
Use high impedance principle
Transformer fed from an earthed source on the star side of transformer.
Stability level : usually max.through fault current of transformer.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
RESTRICTED EARTH FAULT SCHEME
For resistance grounded transformer- base on the typical Fault Current vs. Winding Impedance curve, it shows that
1. Small fault current on HV side of Tx for single phase to ground at LV star.
- HV side O/C relay at cannot detect and clear the fault.
2. The differential relay detect fault < 40% of transformer winding (from transformer terminal).
- Fault current become smaller as the fault closer to the star point (Neutral).
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
RESTRICTED EARTH FAULT SCHEME
For solidly grounded transformer, >> fault current, differential possible to detect ≈ 100% of transformer winding.
REF protection better then Bias Differential scheme to protect Tx star winding . It can detect up to ≈ 80% – 90% of winding fault (E/F) i.e. from TX terminal.
Another 10% - 20% of the winding can be detected by Bucholz relay. - very low fault current
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
Rs
64 Is = 0.1AVo
REF Zone of protection
REF using Kichoff current principle
“Total current enter a network must be same as total current living it”. It operation using circulating current
2 side of CT req. (Line CT & Neutral CT)– measure input vs output
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
RCT = Internal CT resistance
Rl = Wiring / lead resistance
RS = Stabilizing Resistance
VS = Stabilizing Voltage
Stabilizing resistance use to limit the operating current.
To calculate the stabilizing resistor, assumption made that one of the CT saturated with heaviest through fault current.
Vsetting = IF (2Rl + RCT) , where IF normally= 15 X MVA√3 X kV
Highest value of Rl (loop resistance ) and RCT are chosen so to give maximum voltage across the relay under maximum through fault current.
Choose that the minimum operating current = IsAlso that Vs = Is (RS + R64 )Stabilizing resistor RS = (VS / IS ) – R64
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
For stability Vs > V. Hence the stability of REF depends upon Vs voltage setting across the relay circuit during high through fault current that cause one of the CT saturated.
Vkp req. = 2 x Vs = 2 x IF (2Rl + RCT)
Factor 2 Vs is to ensure that during fault the CT used still can derive output current.
V
Im
Vs
Vkp
Selection of CT Knee point Voltage Vkp
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
RS
64
VS
R Y B N
ImR ImY ImBImN
IR
EFFECTIVE PRIMARY OPERATING CURRENT (POC).
The relay operates with IR and Vr. During in zone fault the magnetizing current required to develop voltage Vr across the relay or Vs across the relay circuit are
ImR + ImY + ImB + ImN
Therefore effective POC = N (ImR + ImY + ImB + ImN + IR)POC implies the sensitivity of the scheme.
Example:IR = 20mA, CT Ratio N = 500/1 and Vs = 80V and all CT required 10mA to develop the setting voltage. Then
The effective POC = 500/1 (4x10mA + 20mA)= 30A
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF Setting - Current operating REF Relay
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
Rs
64Vs
i). Determine the voltage setting Vs using
Vs = (IF. /N).(2Rl + RCT)
Where - N = CT ratio- IF = Max. through fault current desired before unstable which normally set to 15 times of transformer rated current.- Rl = max. CT pilot lead resistance.- RCT = CT internal resistance.
Normally,Iop fix to 200mA
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF Setting - Current operating REF Relay
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
ii). Determine the magnetizing current for all CTs at setting Voltage Vs (using CT mag. Curve result). So the total magnetizing current at VS
Im = ImR + ImY + ImB + ImN
iii). Relay current setting IR should be
IR = (IPOC/N) - Im
Typical Setting for REF Protection: Solidly earthed - 10-60% of winding rated
current. (From ESI 48-3 1977)
Resistance earthed - 10-25% of minimum earth fault current for fault at transformer terminals.
iv). Required stabilizing resistor RS will be
VS = IR (RS + R64)RS = (VS/ IR) - R64 Ω
RS power rating P = IR2 . RS (watt)
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF Setting - Voltage operating REF Relay
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
i). Determine the voltage setting Vs using
Vs = (IF. /N).(2Rl + RCT) Where - N = CT ratio- IF = Max. through fault current desired before unstable which normally set to 15 times of transformer rated current.- Rl = max. CT pilot lead resistance.- RCT = CT internal resistance.
Rs
64Vs
IR Is
Normally, Iop fix to 20mA,Vset = 200V
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF Setting - Voltage operating REF Relay
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
ii). Determine the magnetizing current for all CTs at setting Voltage Vs (using CT mag. Curve result). So the total magnetizing current at VS
Im = ImR + ImY + ImB + ImN
iii). If desire effective IPOC > IR + Im then required shunt stabilizing resistor.
iv). Required stabilizing resistor RS will be
Normally relay operating current IR is fix for voltage operated relay
Let IS = (IPOC/N) – (Im+ IR)RS = (VS/ IS) Ω
RS = VS/ ((IPOC/N) – (Im+ IR)) Ω
RS rating P = IS2 . RS (watt)
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
R S
64
R S64
A
V
A
V
a. Relay secondary Injection test.To ensure relay in good working condition with
- operate at setting values with acceptable tolerance- correct connection
1). Relay Operation Test (secondary)
Current Operated Voltage Operated
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
a. Relay secondary Injection test.
i. Injection without stabilizing resistor Rs.
ii. Measure operating current and voltage.iii. Injection with stabilizing resistor.iv. Measure operating current and voltage.v. Compare the measured values with setting values.
i.e. Operating voltage between i. and iii, Vo (iv) > Vo (ii)Operating current Io ≈ Is (setting)Operating voltage Vo ≈ Vs (setting)Vo / Io ≈ Rs (Stabilizing Resistor Value)Secondary test Operating
Voltage Vo (V)Operating
Current Io (A)Resistance
Value
Without Stabilizing Resistor
With Stabilizing Resistor
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
a. Secondary Injection test.
Primary Operating Current Check (Secondary Injection)
Primary Operating Current IPOC = N. IS (where N = CT ratio).Note: The IPOC for future check.
RS
64
VS
R Y B NImR
ImY
ImB
ImNIR
A Is
SecondaryInjectionTest Set.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
b. Primary Injection test
Primary Injection – To check relay operation using secondary output current from CT.
Using Primary Injection Test Equipment.
Injection involve all CTs connected to the scheme.
1000/1Primary Injection
Rs
64 Is = 0.1AVo
Operating current I(primary) = Is x N
CT ratio = N/1
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
c. REF Scheme Stability test.
Rs
64Vo
Fault
Rs
64Vo
Fault
Stable Condition for External Fault. Unstable Condition for Internal Fault.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
c. REF Scheme Stability test.
-Using 1Ø primary test set.
-Injection can be done at phase side or neutral side of Txmer.
-Hi Txmer impedance. Bypass winding req.
-Measure current that flow though all branches-Phase current-Neutral current-Relay current
- Measure voltage across the relay and stabilizing resistor.
1Ø Primary Injection
Rs
64VoBypass Tx. winding
1Ø Primary Injection
Rs
64Vo
Stable Condition Unstable Condition
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
REF Scheme – Current Flow
RS
64VS
Stable: REF Secondary connection and current flow for out zone fault.
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
REF Scheme – Current Flow
Unstable: Due to wrong connection at Neutral CT side.
RS
64
VS
Wrongconnection
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
REF Scheme – Current Flow
Unstable: Due to wrong connection at Line or Phase CT side.
RS
64
VS
Wrongconnection
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
REF SCHEME TEST.
HI-IMPEDANCE RESTRICTED EARTH FAULT PROTECTION SCHEME. Cont.
REF Scheme – Current Flow
Unstable: Due to primary equipment defect. Fault current by passing Neutral CT.
VSRS
64
Institut Latihan TNB - ILSAS
Unit Perlindungan, Seksyen Latihan Penghantaran 2007 Zulkarnain Ishak
Rumusan
- Pengetahuan terhadap skim perlindungan REF penting untuk diketahui oleh Jurutera / Juruteknik Perlindungan yang berkecekapan didalam memastikan pepasangan skim perlindungan tersebut beroperasi didalam keadaan yang diharapkan.