REKABENTUK PEMASANGAN
ELEKTRIKOleh:
RAIS BIN MAAT
Institut Latihan dan Pembangunan
Infrastruktur Ikram (ITiDi)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
2/132
Jun2002 ITiDi 2
CIRI-CIRI PEPASANGAN
Kos effective
Selamat digunakan
Mengikut peraturan Praktikal, mesra pengguna
Mudah & murah disenggara
Nilai estetik
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
3/132
Jun2002 ITiDi 3
PERATURAN BERKAITAN
IEE ke 16
Akta Bekalan Elektrik 1990
Peraturan-Peraturan Elektrik 1994 Factories and Machinery Act 1967
British Code of Practice
British Standard/Malaysian Standard Illumination Engineering Society (IES)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
4/132
Jun2002 ITiDi 4
LANGKAH-LANGKAH
Kira Jumlah Beban Tersambung (TCL) dan
Kehendak Maksima (MD) pepasangan
Tentukan bilangan dan kedudukan bebanelektrik seperti lampu-lampu, kipas, soket
outlet 13A dan sebagainya Tentukan lokasi suis, DB, SSB, MSB,
Pencawang, dsb.
Tentukan jenis & kadaran arus (currentrating) alat perlindungan/pemutus litar yanghendak digunakan
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
5/132
Jun2002 ITiDi 5
LANGKAH-LANGKAH
Pilih jenis kabel, saiz dan bilangan untuk
setiap bahagian pemasangan serta jenis
pendawaian
Tentukan beban (lampu) dan suis yangmengawalnya
Sediakan lukisan-lukisan elektrik (site
plan, rajah skema & rajah susunatur)
Sediakan anggaran kos projek
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
6/132
Jun2002 ITiDi 6
ANGGARAN BEBAN
Lampu-lampu
Kipas-kipas (siling/dinding/pelawas)
Soket alir keluar (13A & 15A)
Alat hawa dingin
Motor elektrik
Pengasing (Isolator) Mesen-mesen
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
7/132
Jun2002 ITiDi 7
BEBAN-BEBAN KECIL
Loceng Abaikan
Jam elektrik Abaikan
Mata lampu (tanpa lampu tersedia) 100 W
18W flourescent 25 W
36W flourescent 50 W
60W filament 60 W
100W filament 100 W
Emergency light/KELUAR sign 20 W
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
8/132
Jun2002 ITiDi 8
BEBAN-BEBAN KECIL
Kipas siling/dinding 90 W
Mata kipas siling 100 W
Soket alir keluar 13A 250 W (domestik)
300 W (industri)
Soket alir keluar 15A 500 W
Mata alat hawa dingin 1.2 kW (1.5h.p), 1.5 kW (2h.p),
1.9kW (2.5h.p), 2.3kW (3h.p)
Isolator 30A 2.3 kW
Isolator 60A 3.7 kW
Lain-lain Ikut arus kadaran
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
9/132
Jun2002 ITiDi 9
BEBAN LAMPU DISCHARGE
Untuk anggaraan beban lampu discharge
kadaran wattnya hendaklah didharab
dengan faktur 1.8 untuk mengambil kira
faktur kuasa lampu, kehilangan didalam
cok atau ballast dan kesan harmonic
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
10/132
Jun2002 ITiDi 10
BEBAN-BEBAN BESAR
Untuk beban besar nilai kuasa
sebenarnya (kW/kVA), voltan bekalan,
faktur kuasa dan kecekapannya
hendaklah diketahui terlebih dahulu dantidak boleh menganggarnya begitu
sahaja
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
11/132
Jun2002 ITiDi 11
TCL
Total Connected Load (TCL) ialahjumlah beban anggaran (kW)
dengan andaian kesemua beban-
beban elektrik didalam sesuatupemasangan elektrik digunakan
secara maksima dan serentak
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
12/132
Jun2002 ITiDi 12
FAKTUR KEPELBAGAIAN (DF)
Ialah satu angka atau peratus yang
menggambarkan kuasa tertinggi dari
TCL yang digunakan serentak pada satu-
satu masa tertentu Contohnya 100 buah lampu 100W yang
dipasang hanya 80 buah sahaja di ON
kan serentak pada satu-satu masa. Olehitu DF adalah 80% atau 0.8
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
13/132
Jun2002 ITiDi 13
KEHENDAK MAKSIMA (MD)
MD ialah Beban Maksima (kW) yangdiperlukan oleh sesuatu pepasangantanpa mengira bila ianya akan berlaku.
MD lazimnya adalah beban penuh danmungkin jugak lebih dari itu. Ialazimnya kurang atau paling tinggi samadengan TCL.
MD = TCL x DF
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
14/132
Jun2002 ITiDi 14
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
15/132
Jun2002 ITiDi 15
MENENTUKAN MD
Dalam rekabentuk MD lazimnya tidak dapat
ditentukan dengan tepat. Nilai MD hanyalah satu
nilai anggaraan sahaja berdasarkan jadual atau
pengalaman atau data-data tertentu. Namun bagiperekabentuk yang berpengalaman mereka boleh
menentukan nilai MD yang lebih baik dan realistik
walaupun tidak seratus peratus tepat. Nilai MD
pula boleh berubah apabila pola penggunaanberubah. Nilai MD penting untuk menentukan
kadaran pemutus litar utama
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
16/132
Jun2002 ITiDi 16
PERTAMBAHAN BEBAN
Setelah MD dapat dianggarkan ia
hendaklah ditambah 10% hingga 15%
lagi untuk mengambil kira pertambahan
beban dimasa akan datang. Jikaanggaran MD terlalu rendah mungkin
pemutus litar tidak dapat menahan arus
beban penuh, sebaliknya jika anggaraanMD terlalu tinggi pemasangan menjadi
oversize, membazir dan tidak perlu
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
17/132
Jun2002 ITiDi 17
BEBAN ALAT HAWA DINGIN
Jika pehak mekanikal lambat atau belumdapat menganggarkan beban alat hawa
dingin mereka, formula berikut boleh
digunakan, tetapi hanya untukketinggian siling standard 9 kaki:
kW = 0.044615 x luas lantai (m)
Beban sebenarnya hendaklah diperolehi
dari pehak mekanikal
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
18/132
Jun2002 ITiDi 18
ESSENTIAL & NON-
ESSENTIAL LOADS
Essential Loads Loads that need supply atall times especially during normal supplyfailure such as corridor lights, computers,
servers, PABX, security system, life supportequipment, operation room, etc.
Non-Essential Loads Less important loadsthat do not require supply during normal supply
failure such as normal office lightings, officeair cond system, etc
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
19/132
Jun2002 ITiDi 19
SUPPLY FOR ESSENTIAL
LOADS
Normally essential loads get immediate
supply from UPS system
(Uninterruptable Power Supply) for ashort duration and will be taken over by
standby generator set after that.
Different busbar shall be used to supply
these loads and change over contactor
shall be used
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
20/132
Jun2002 ITiDi 20
MENGIRA ARUS
Gunakan formula:
P (kW) = Vph x Iph x Cos (satu fasa)
dan untuk tiga fasa:P (kW)= 3 x Vline x Iline x Cos
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
21/132
Jun2002 ITiDi 21
KEDUDUKAN LAMPU
Bilangan lampu ditentukan menggunakanLumen Method atau cara lain yang sesuai.
Kedudukan dan susunan lampu hendaklah
sesuai dengan pencahayaan samarata dantidak bertindih dengan peralatan lain seperti
grill air-cond, kipas siling dsb.
Kedudukan suis hendaklah ditempat senang di
akses dan tidak terlindung / terhalang.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
22/132
Jun2002 ITiDi 22
KEDUDUKAN MATA KUASA
Didalam satu bilik mata kuasa hendaklahdari fasa yang sama, jika dua mata kuasa
dari fasa yang berlainan jaraknya
hendaklah tidak kurang dari 2 meter. Jarak dari pili air dan dapor hendaklah
tidak kurang dari 2 meter.
Tidak dibenarkan dipasang didalam bilikmandi kecuali untuk shaver unit.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
23/132
Jun2002 ITiDi 23
KEDUDUKAN MATA KUASA
Soket outlet 13A yang TIDAK dipasangdidinding hendaklah menggunakan
underfloor ducting/conduit/casing atau
apa-apa cara yang sesuai dan diluluskan Cara ini diperlukan untuk bilik
komputer, makmal, woksyop,
supermarket dan sebagainya
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
24/132
Jun2002 ITiDi 24
SOKET BILIK KOMPUTER
Bilik komputer selalunya memerlukanbilangan soket 13A yang banyak, oleh itu
lebih baik dikhaskan satu DB untuknya.
Penggunaan RCCB 30mA mungkinmenimbulkan masaalah disebabkan arus
bocor yang tinggi, oleh itu RCCB 100mA
boleh digunakan.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
25/132
Jun2002 ITiDi 25
LOKASI MSB, SSB, DB
MSB hendaklah dekat dengan pusatbeban (load centre) untuk mengelakkan
susut voltan yang melebehi 4%.
SSB hendaklah digunakan jikasekumpulan beban berada agak jauh
dari pusat beban untuk mejimatkan
kabel dan memudahkan kawalan dansenggaraan.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
26/132
Jun2002 ITiDi 26
DISTRIBUTION BOARD (DB)
Jika bilangan lampu dan soket 13Abanyak eloklah DB yang berasingandigunakan untuk memudahkan kerja-
kerja senggaraan. Penggunaan RCCB tiga fasa tidak
digalakkan disebabkan gangguan kepadafasa-fasa lain jika berlaku tripping.Gunakan tiga RCCB satu fasa untuk DBtiga fasa.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
27/132
Jun2002 ITiDi 27
PERINGKAT AGIHAN BEKALAN
Bekalan dari TNB/Alatubah/Janakuasa
Ke Papan Suis Utama (PSU/MSB)
Ke Papan Suis Kecil (PSK/SSB)
Ke DB atau beban besar
Ke beban-beban melalui alat kawalan
atau pensuisan
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
28/132
Jun2002 ITiDi 28
JENIS-JENIS PSU
Tiada kompartmen
Sebahagian sahaja berkompartmen
Sepenuhnya berkompartmen
Wall mounted
Pedestal (floor mounted), front access
Cubicle (front & back access) Cubicle (front access only)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
29/132
Jun2002 ITiDi 29
CUBICLE SWITCHBOARD
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
30/132
Jun2002 ITiDi 30
PEDESTAL
SWITCHBOARD
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
31/132
Jun2002 ITiDi 31
WALLMOUNTED
SWITCHBOARD
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
32/132
Jun2002 ITiDi 32
PEMILIHAN KABEL
Jenis-Jenis Kabel:PVC, PVC/PVC, PVC/SWA/PVC
PILC (Paper Insulated Lead Covered)
PILCDSTAS ( Double Steel Tape &Amoured)
XLPE (Cross Link Polyethylene)
XLPE/SWA/PVC
MICC (Mineral Insulated Copper Cable)FRC (Fire Rated cable)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
33/132
Jun2002 ITiDi 33
JENIS-JENIS PENDAWAIAN
Permukaan (surface)
Terbenam (consealed)
Pembuluh permukaan (surface conduit)
Pembuluh terbenam (consealed conduit) Sesalur (trunking)
Ducting
Dulang (tray)
Riser/duct/trench
Busduct/Ladder
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
34/132
Jun2002 ITiDi 34
PENDAWAIAN
PERMUKAAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
35/132
Jun2002 ITiDi 35
PENDAWAIAN
TERBENAM
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
36/132
Jun2002 ITiDi 36
PENDAWAIAN
KONDUIT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
37/132
Jun2002 ITiDi 37
PENDAWAIAN TRUNKING DAN TRAY
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
38/132
Jun2002 ITiDi 38
SAIZ KABEL
Kabel hendaklah cukup saiznya supaya:Boleh menanggung arus beban penuh
dan arus pusuan (inrush current)
Keupayaan membawa arusnyamelebehi dari keupayaan membawa
arus pemutus litar yang mengawalnya
Susut voltan tidak melebihi 4%
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
39/132
Jun2002 ITiDi 39
KABEL LITAR AKHIR
Litar Fius/MCB Kabel (mm) Luas LantaiLampu &
kipas
5A/6A 1.5 -
Litar gelang(soket 13A)
30/32A 2.5 100m
Litar radial
soket 13A
30/32A 4.0 50m
Radial soket
13A
20A 2.5 20m
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
40/132
Jun2002 ITiDi 40
SAIZ KABEL PERLINDUNGAN
Saiz kabel fasa (S) Saiz kabel perlindungan
Kurang dari 16mm S
16mm - 35mm 16mm
Melebihi 35mm Separuh dari S
Lebih dari 70mm
pita tembaga 6mm x 25mm
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
41/132
Jun2002 ITiDi 41
KABEL PENGIKAT
Kabel Pengikat (Bonding Conductor)hendaklah sama saiz dengan kabel
perlindungan tetapi minima 4.0mm.
Ia digunakan untuk menyambunganbahagian-bahagian logam berkonduktif
dengan terminal bumi sepunya (common
earthing terminal) untuk mengujudkanvoltan samaupaya.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
42/132
Jun2002 ITiDi 42
SAIZ KABEL-KABEL LAIN
Ib
In = ------------------------
Ca + Cg + CiDimana : Ib = arus beban
Ca = faktur suhu ambient
Cg = faktur kumpulanCi = faktur penebat haba
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
43/132
Jun2002 ITiDi 43
SUSUT VOLTAN
Vd = mV x I x L
1000Vd - jumlah susut voltan (tak melebihi 4%)
mV - susut voltan kabel (milivolt/A/m)
I - arus beban (A)
L - panjang kabel (meter)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
44/132
Jun2002 ITiDi 44
CARA CEPAT
mV = 1000 x Vd
A x L
Dimana nilai Vd maksima
ditetapkan dahulu
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
45/132
Jun2002 ITiDi 45
CONTOH
Satu beban 18kW, 415V, p.f 0.85 berada90 meter dari MSB. Tentukan saiz kabel jenis PVC multicore tanpa perisai yangsesuai digunakan.
I = 18,000/1.732x415x0.85 = 30A
Dari jadual 4D1A, IEE 16, column 5 (3
atau 4 kabel tertutup dlm. konduit atautrunking) saiz kabel yang sesuai ialah6mm
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
46/132
Jun2002 ITiDi 46
CONTOH
Keupayaan membawa arus kabel 6mm
ialah 36A, oleh itu ia mampu membawa arus
tadi (30A)
Tetapi nilai susut voltannya ialah 6.4
milivolt/ampiar/meter (JADUAL 4D1B,
column 6)
Jumlah susut voltan Vd= 0.0064V x 30A x
90m = 17.28V (melebihi 4% atau 16.6V), olehitu kabel 6mm tidak boleh digunakan
CONTOH
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
47/132
Jun2002 ITiDi 47
CONTOH Oleh itu pilih saiz 10mm atau 16mm, tetapi cara
ini lambat dan membuang masa Oleh itu gunakan cara cepat:
mV = 1000 x (susut voltan maksima 16V) = 5.9mV
30A x 90m
Dari JADUAL 4D1B, column no 6, reference
method 3 or 4, nilai mV yang diperolehi tadi berada
diantara 6.4mV(6mm) dan 3.8mV(10mm) dan saiz
yang boleh dipilih ialah 10mm sebab susutvoltannya kurang dari 5.9mV. Lebih besar saiz
kabel maka lebih kuranglah susut voltannya
SAIZ KONDUIT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
48/132
Jun2002 ITiDi 48
SAIZ KONDUIT
Saiz konduit G.I atau PVC adalah terhad
kepada maksima 32mm dan hanya boleh diisidengan kabel sebanyak 40% sahaja
Jadual 12A memberikan faktur kabel untuk
konduit tiada bengkok kurang dari 3 meter Jadual 12B memberikan faktur kabel untuk
konduit untuk digunakan dengan Jadual 12A
Jadual 12C memberikan faktur kabel untuk
konduit melebehi 3 meter
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
49/132
Jun2002 ITiDi 49
SAIZ KONDUIT
Gunakan appendix 12 IEE
Jadual 12A
Jadual 12B
Jadual 12C
Jadual 12E
Jadual 12F
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
50/132
Jun2002 ITiDi 50
SAIZ-SAIZ KONDUIT
STANDARD
16mm
20mm
25mm
32mm
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
51/132
Jun2002 ITiDi 51
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
52/132
Jun2002 ITiDi 52
CONTOH
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
53/132
Jun2002 ITiDi 53
CONTOH
Tentukan saiz konduit untuk memuatkan 9
bilangan kabel PVC 1.5mm stranded,anggapkan konduit terdapat satu bengkokan
(one bend)
Dari Jadual 12A, kabel 1.5mm PVCfakturnya ialah 31, jumlah fakturnya
ialah 9 x 31= 279, rujuk table 12D kita
dapati angka yang paling hampir ialah294, oleh itu saiz konduit yang paling
sesuai ialah 20mm
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
54/132
Jun2002 ITiDi 54
SAIZ-SAIZ TRUNKING
(mm x mm)
50 x 37.5 50 x 50
75 x 50 75 x 75
100 x 50 100 x 75 100 x 100
150 x 50 150 x 75 150 x 75
150 x 100 150 x 150
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
55/132
Jun2002 ITiDi 55
PAPAN AGIHAN
Kabel masuk
Pengasing/Suis Utama Berfius/MCB
RCCB
Palang bas hidup Fius/MCB
Terminal Neutral
Terminal bumi Numbering & Labelling
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
56/132
Jun2002 ITiDi 56
PAPAN AGIHAN SATU FASA
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
57/132
Jun2002 ITiDi 57
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
58/132
Jun2002 ITiDi 58
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
59/132
Jun2002 ITiDi 59
PAPAN
AGIHAN
TIGAFASA
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
60/132
Jun2002 ITiDi 60
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
61/132
Jun2002 ITiDi 61
TYPICAL
MAIN
SWITCH
BOARD
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
62/132
Jun2002 ITiDi 62
ONE INCOMING WITH GENSET
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
63/132
Jun2002 ITiDi 63
TWO INCOMING WITH GENSET
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
64/132
Jun2002 ITiDi 64
TYPICAL MAIN SWITCHBOARD WITH GENSET
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
65/132
Jun2002 ITiDi 65
BUSBAR SYSTEM
Single busbar system
Sectionalised single busbar system
Sectionilised ring busbar system
Duplicate busbar system
KADARAN ARUS BUSBAR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
66/132
Jun2002 ITiDi 66
KADARAN ARUS BUSBAR
Saiz Busbar (mm x mm) Kadaran Arus (A)
6.3 x 40 4006.3 x 50 500
6.3 x 63 600
6.3 x 70 7006.3 x 80 800
6.3 x 90 900
6.3 x 100 10002 x 6.3 x 63 1200
2 x 6.3 x 80 1600
MINIMUM CLEARANCE INDOOR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
67/132
Jun2002 ITiDi 67
BUSBAR OPEN OR ENCLOSED
Voltage (kV)
Between Phase
Min clearance to
earth in air
Min clearance to
earth in air
Min
ClearanceBetweenphase in air
Min
ClearanceBetweenphase in air
Open (in) Enclosed (in) Open (in) Enclosed (in)
0.44 0.75 5/8 1.0 0.75
0.66 1.0 0.75 1.25 1.02.2 1.5 1.5 1.5 1.5
3.3 2.0 2.0 2.0 2.0
6.6 2.5 2.5 3.5 3.511 3.0 3.0 5.0 5.0
22 5.5 5.5 9.5 9.5
33 8.75 8.75 14 14
MINIMUM CLEARANCE OUTDOOR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
68/132
Jun2002 ITiDi 68
MINIMUM CLEARANCE OUTDOOR
BUSBAR OPEN TYPE
Voltage (kV)
Between Phase
Min clearance to
earth in air (in)
Min clearance
bet. phase in air
6.6 6 8
11 7 11
22 9 17
33 13 23
MINIMUM CLEARANCE BETWEEN BUSBAR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
69/132
Jun2002 ITiDi 69
MINIMUM CLEARANCE BETWEEN BUSBAR
IMMERSED IN COMPOUND OR OIL
Voltage (kV)
Between Phase
Min clearance to
earth (in)
Min clearance
bet. phase (in)
0.66 0.5 0.75
3.3 0.5 0.75
6.6 0.75 1.0
11 1.0 1.5
22 1.75 2.5
33 2.5 3.5
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
70/132
Jun2002 ITiDi 70
MELTING POINT OF COPPER
Melting point of copper is at 1,084 degrees
C
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
71/132
Jun2002 ITiDi 71
COPPER VS ALUMINIUM
CU AL
Weight for equal conductivity 1.0 0.5
Conductivity for equal areas 1.0 0.61
Tensile strength (hard drawn) 1.0 0.4
Hardness (hard drawn) 1.0 0.44
Modulus of elasticity 1.0 0.55
Co-efficient of thermal expansion 1.0 1.39
Melting point 1.0 0.61
SISTEM PERLINDUNGAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
72/132
Jun2002 ITiDi 72
SISTEM PERLINDUNGAN
Overcurrent (O/C)/Litar pintas
Overload
Earth Leakage (arus bocor kebumi)
Earth Fault (rosak ke bumi)
Lightning
Surge
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
73/132
Jun2002 ITiDi 73
ALAT PERLINDUNGAN
Fius (fius suis, suis fius) MCB (miniature c.b)
MCCB (moulded case c.b)
ACB (air circuit breaker)
RCCB (residual current c.b)
Current Transformer (C.T)
Relay
SPD (surge protection device)
PEMILIHAN ALAT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
74/132
Jun2002 ITiDi 74
PEMILIHAN ALAT
PERLINDUNGAN
Arus kadaran (current rating)
kA rating
Harga
Mudah disenggara
Trend terkini
Praktikaliti/Kesesuaian Technical performance
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
75/132
Jun2002 ITiDi 75
FAKTUR FIUS
Ialah arus minima yang akan meleburkan
elemen fius dibahagikan dengan arus
kadaran fius. Fius dawai - 2
Fius katrij - 1.5
Fius HRC - 1.25 ke 1.5
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
76/132
Jun2002 ITiDi 76
KADARAN FIUS SUIS
100A
160A
250A
300A
400A
600A
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
77/132
Jun2002 ITiDi 77
KADARAN MCB
6A
10A
15A
20A
32A
KADARAN MCCB
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
78/132
Jun2002 ITiDi 78
KADARAN MCCB
30A 300A
60A 400A
100A 500A
125A 600A
150A 800A
200A 1000A 250A 1200A
KADARAN ACB
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
79/132
Jun2002 ITiDi 79
KADARAN ACB
600A 3000A
800A 3500A
1000A 4500A
1250A 6300A
1600A
2000A 2500A
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
80/132
Jun2002 ITiDi 80
BUS TIE/BUS COUPLER
Jika sesuatu pemasangan itu mendapat dua
atau lebih punca bekalan TNB kedua-dua
nya boleh dihubungkan menggunakan bus
tie/bus coupler dan hendaklah dari jenisempat kutub. Sistem ini hendaklah dipasang
dengan castle key untuk mengelakkan
kedua-dua bekalan dari bertembung tanpasynchronising dibuat terlebih dahulu
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
81/132
Jun2002 ITiDi 81
CHANGE OVER CONTACTOR
Jika sesuatu pemasangan perlu
mempunyai janakuasa tunggusedia
bekalannya hendaklah disambungkan
kepada MSB menggunakan change overcontactor (C.O.C) untuk operasi secara
otomatik dan hendaklah dari jenis empat
kutub
DISKRIMINASI
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
82/132
Jun2002 ITiDi 82
DISKRIMINASI
Menentukan tahap arus atau arus &masa disetiap bahagian litar supaya jika
berlaku gangguan bekalan akan
melibatkan hanya bahagian yang kecildan tidak melibatkan bahagian-bahagian
lain yang tidak berkaitan.
DISKRIMINASI
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
83/132
Jun2002 ITiDi 83
DISKRIMINASI
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
84/132
Jun2002 ITiDi 84
DISKRIMINASI
FAULT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
85/132
Jun2002 ITiDi 85
DISKRIMINASIARUS & MASA
PERLINDUNGAN LITAR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
86/132
Jun2002 ITiDi 86
PERLINDUNGAN LITAR
AKHIR Untuk perlindungan arus lebih/ beban
lebih - menggunakan fius berkadaran 5A,
10A, 15A, 20A,30A, 63A atau MCBberkadaran 6A, 10A, 15A, 20A, 32A, 60A
Untuk perlindungan bocor ke bumi
menggunakan RCCB berkepekaan 30mAatau 100mA
PERLINDUNGAN LITAR AKHIR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
87/132
Jun2002 ITiDi 87
PERLINDUNGAN LITAR AKHIR
Fius/MCB Kabel Had Kuasa
5/6A 1.5mm 10 mata lampu/kipas, TCL maksima 1000/1200W15A 2.5mm 1 bil s/s/o 13A
20A 2.5mm 2 bil s/s/o 13A
30A (ring) 2.5mm 10/Tiada had tetapi dalam ruang 100m persegi
30A (radial) 4.0mm 6 bil s/s/o 13A15A 2.5mm 1 bil cooker unit < 3kW
15A 4.0mm 1 bil s/o 15A
15A 4.0mm 1 bil 1.5kW water heater
15A 4.0mm 1 bil 1.5h.p penghawa dingin30A 6.0mm 1 bil 2.5h.p penghawa dingin
30A 6.0mm 1 bil 3.0h.p penghawa dingin
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
88/132
Jun2002 ITiDi 88
TINGKAT
BAWAH
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
89/132
Jun2002 ITiDi 89
TINGKAT
SATU
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
90/132
Jun2002 ITiDi 90
TINGKAT
DUA
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
91/132
Jun2002 ITiDi 91
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
92/132
Jun2002 ITiDi 92
KIRAAN BEBAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
93/132
Jun2002 ITiDi 93
Item Qty TCL DF MD (kW)
1x40W(F) 3 3x50W 100% 0.152x40W (F) 14 14x50W 100% 0.7
Exhaust fan 6 6x90W 100% 0.54
Soket 13A 9 9x250W 80% 1.8
Air cond 1hp 1 1x1.2kW 100% 1.2
Air cond 2hp 2 2x1.5kW 100% 3.0
Air cond 2.5hp 2 2x1.9kW 100% 3.8
JUMLAH 11.18kW
KIRAAN BEBAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
94/132
Jun2002 ITiDi 94
KIRAAN BEBAN
Jumlah MD = 11.18kW
Arus beban penuh (I):
I = 11,180W 240V = 46.58A
BILANGAN HALA PAPAN AGIHAN
No Kadaran Beban Kabel
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
95/132
Jun2002 ITiDi 95
Litar Fius/MCB (mm)
1 6A 7nos 2x40W(F) + 3nos 1x40W(F) 1.5
2 6A 7nos 2x40W(F) 1.5
3 6A 6 nos exhaust fan 1.5
4 6A spare
5 6A spare
6 32A(ring cct.) 5nos 13A s/s/o 2.5
7 32A(ring cct.) 4nos 13A s/s/o 2.5
8 32A spare
9 32A spare
10 20A 1no 1.0hp air cond point 4.0
11 20A 1no 2.0hp air cond point 4.0
12 20A 1no 2.0hp air cond point 4.0
13 32A 1no 2.5hp air cond point 6.014 32A 2no 2.5hp air cond point 6.0
15 32A spare
16 32A spare
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
96/132
Jun2002 ITiDi 96
AGIHAN
BEBAN
SEIMBANG
ANTARA
FASA
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
97/132
Jun2002 ITiDi 97
PERLINDUNGAN SUB MAIN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
98/132
Jun2002 ITiDi 98
PERLINDUNGAN SUB MAIN
Menggunakan Fius Suis (F/S) atauMCCB dengan geganti ELR dan
alatubah arus Z
Menggunakan ACB jika beban sub mainadalah besar
Menggunakan Oil Dash Pot relay
E/F relay jenis IDMT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
99/132
Jun2002 ITiDi 99
OIL
DASH
POT
RELAY
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
100/132
Jun2002 ITiDi 100
EARTH
LEAKAGE
RELAY
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
101/132
Jun2002 ITiDi 101
IDMT
RELAY
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
102/132
Jun2002 ITiDi 102
IDMT
RELAY
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
103/132
Jun2002 ITiDi 103
EARTH
FAULT
RELAY
PERLINDUNGAN SOLID
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
104/132
Jun2002 ITiDi 104
EARTHING
Perlindungan earth leakage/earth faulttanpa menggunakan geganti , ELCB atau
RCCB
Hanya menggunakan fius atau MCB
Sistem pembumian mestilah baik
Rintangan elektrod bumi mestilah
serendah mungkin
Untuk saiz pemasangan yang kecil
RCCB/ELCB
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
105/132
Jun2002 ITiDi 105
RCCB/ELCB
13A, 2 kutub, 10mA untuk alatpermainan kanak-kanak.
40A/43A, 2 kutub, 30mA untuk litarsoket alir keluar 13A secara individuatau berkumpulan.
60A/63A, 2 kutub, 100mA untuk DB satufasa lampu, kipas dan soket alir keluar.
60A/63A, 4 kutub, 300mA.
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
106/132
Jun2002 ITiDi 106
RCCB
PERLINDUNGAN KILAT
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
107/132
Jun2002 ITiDi 107
PERLINDUNGAN KILAT
Bangunan melebihi 2 tingkat atau Bangunan ditempat tinggi atau
Bangunan dikawasan lapang seperti
sawah padi Air finial, horizontal conductor, down
conductor, inspection point, earthchamber, earth electrode. Copper tape,
Aluminium tape or G.I wire.
ARUS/VOLTAN PUSUAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
108/132
Jun2002 ITiDi 108
ARUS/VOLTAN PUSUAN
Apabila berlaku arus/voltan pusuan(current/voltage surge) peralatan mudah
rosak
Surge suppressor Lightning arrester
Surge diverter
LUKISAN ELEKTRIK
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
109/132
Jun2002 ITiDi 109
LUKISAN ELEKTRIK
Standard symbol Schematic diagram
Workshop drawing
Wiring diagram
Layout diagram
Key plan/Site plan
KOD WARNA
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
110/132
Jun2002 ITiDi 110
KOD WARNA Merah untuk fasa merah atau wayer
hidup
Kuning untuk fasa kuning
Biru untuk fasa biru
Hitam untuk neutral (tiga fasa)
Coklat untuk wayer hidup (satu fasa)
Biru untuk wayer neutral (satu fasa) Hijau / hijau berjalur kuning untuk bumi
KETINGGIAN PERALATAN
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
111/132
Jun2002 ITiDi 111
Peralatan tergantung di siling 240cm (8ka)Peralatan terlekat di dinding 205cm (6ka 9in)
Suis lampu/kipas 145cm (4ka 9in)
Soket alir keluar 145cm (4ka 9in)
Soket alir keluar 30cm (1ka)
Papan agihan 205cm (6ka 9in)
BILL OF QUANTITIES (B.Q)
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
112/132
Jun2002 ITiDi 112
BILL OF QUANTITIES (B.Q)
Untuk memudahkan membuat anggarandan menyemak perubahan serta
penambahan/pengurangan kuantiti
Memudahkan pemborong membuatsebutharga kerja
Mengelakkan keraguan daripada
perkara yang kurang jelas
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
113/132
Jun2002 ITiDi 113
B.Q
POWER FACTOR CAPACITOR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
114/132
Jun2002 ITiDi 114
POWER FACTOR CAPACITOR
BANK
Power Factor Capacitor Bank perlu
dipasang untuk mempastikan faktur
kuasa pemasangan tidak rendahdaripada 0.85 kerana jika rendah
daripada itu pehak TNB akan
mengenakan denda kepada pengguna
yang terlibat
TARIFF ELEKTRIK
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
115/132
Jun2002 ITiDi 115
Caj kemasukan bekalan Sumbangan perkhidmatan
Cagaran
kWh (unit) digunakan
kW permintaan maksima (tarif C1)
Caj faktur kuasa rendah dari 0.85
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
116/132
Jun2002 ITiDi 116
SOALAN
Berdasarkan lukisan yang diberikan
dapatkan TCL dan MD sertakan lakarkan
rajah skema SSB bangunan tersebut lengkapdengan saiz kabel, saiz busbar, kadaran arus
pemutus litar incoming dan outgoing serta,
nisbah c.t dan julat (range) alat-alat
pengukuran
SENARAI BEBAN SSB
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
117/132
Jun2002 ITiDi 117
Lokasi/Beban MD MCCB
1. Ground floor 19kW 63A
2. First floor 25kW 63A
3. Second floor 13kW 63A
4. Third floor 13kW 63A
5. Air cond central unit 50kW 200A
6. Water pump 5kW 63A
7. Fire fighting pump 5kW 63A
8. Compound lighting 4kW 63A
SENARAI BEBAN UNTUK MSB
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
118/132
Jun2002 ITiDi 118
Bangunan/Beban MD Jarak
1. Blok pentadbiran 120kW 90m
2. Bangunan akan datang 120kW 130m
3. Bengkel 100kW 210m
4. Dewan akan datang 150kW 120m
5. Kantin 8kW 180m
6. Surau 4kW 230m
7. Pam air 5kW 70m
8. Lampu kawasan 4kW 90m
MCCB & SAIZ KABEL
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
119/132
Jun2002 ITiDi 119
Beban Arus MCCB Kabel V.Drop1. 120kW 196A 250A 120mm o.k
2. 120kW 196A 250A 120mm o.k
3. 100kW 164A 200A 70mm 95mm4. 150kW 246A 300A 150mm o.k
5. 8kW 14A 63A 16mm o.k
6. 4kW 6.5A 30A 10mm o.k
7. 5kW 8A 30A 10mm o.k
8. 3kW 5A 30A 10mm o.k
KADARAN ACB & BUSBAR
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
120/132
Jun2002 ITiDi 120
KADARAN ACB & BUSBAR
Jumlah MD = 510kW
I = 835A
Kadaran ACB = 1250A Saiz busbar : 4 x 2 x 6.3mm x 63mm
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
121/132
Jun2002 ITiDi 121
QUESTION
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
122/132
Jun2002 ITiDi 122
A 4 core PVC/SWA/PVC copper cable is to be
installed from SSB A to a 3 phas 415V motorwith a full load current of 102A and a p.f of0.75lagging, along with two similar fixed to aperforated cable tray, where sheaths would be
touching. Circuit is to be protected by a BSHRC fuse. Cable is 100m, ambient temp. 30 degC, voltage drop from MSB up to SSB A is 9V.
Determine the normal rating of the fuse, size ofcable if total voltage drop from MSB to load isnot to exceed 4%
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
123/132
Jun2002 ITiDi 123
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
124/132
Jun2002 ITiDi 124
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
125/132
Jun2002 ITiDi 125
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
126/132
Jun2002 ITiDi 126
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
127/132
Jun2002 ITiDi 127
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
128/132
Jun2002 ITiDi 128
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
129/132
Jun2002 ITiDi 129
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
130/132
Jun2002 ITiDi 130
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
131/132
Jun2002 ITiDi 131
-
8/2/2019 f307139672_REKABENTUK_ELEKTRIK
132/132