    REKABENTUK PEMASANGAN

    ELEKTRIKOleh:

    RAIS BIN MAAT

    Institut Latihan dan Pembangunan

    Infrastruktur Ikram (ITiDi)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    2/132

    Jun2002 ITiDi 2

    CIRI-CIRI PEPASANGAN

    Kos effective

    Selamat digunakan

    Mengikut peraturan Praktikal, mesra pengguna

    Mudah & murah disenggara

    Nilai estetik

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    3/132

    Jun2002 ITiDi 3

    PERATURAN BERKAITAN

    IEE ke 16

    Akta Bekalan Elektrik 1990

    Peraturan-Peraturan Elektrik 1994 Factories and Machinery Act 1967

    British Code of Practice

    British Standard/Malaysian Standard Illumination Engineering Society (IES)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    4/132

    Jun2002 ITiDi 4

    LANGKAH-LANGKAH

    Kira Jumlah Beban Tersambung (TCL) dan

    Kehendak Maksima (MD) pepasangan

    Tentukan bilangan dan kedudukan bebanelektrik seperti lampu-lampu, kipas, soket

    outlet 13A dan sebagainya Tentukan lokasi suis, DB, SSB, MSB,

    Pencawang, dsb.

    Tentukan jenis & kadaran arus (currentrating) alat perlindungan/pemutus litar yanghendak digunakan

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    5/132

    Jun2002 ITiDi 5

    LANGKAH-LANGKAH

    Pilih jenis kabel, saiz dan bilangan untuk

    setiap bahagian pemasangan serta jenis

    pendawaian

    Tentukan beban (lampu) dan suis yangmengawalnya

    Sediakan lukisan-lukisan elektrik (site

    plan, rajah skema & rajah susunatur)

    Sediakan anggaran kos projek

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    6/132

    Jun2002 ITiDi 6

    ANGGARAN BEBAN

    Lampu-lampu

    Kipas-kipas (siling/dinding/pelawas)

    Soket alir keluar (13A & 15A)

    Alat hawa dingin

    Motor elektrik

    Pengasing (Isolator) Mesen-mesen

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    7/132

    Jun2002 ITiDi 7

    BEBAN-BEBAN KECIL

    Loceng Abaikan

    Jam elektrik Abaikan

    Mata lampu (tanpa lampu tersedia) 100 W

    18W flourescent 25 W

    36W flourescent 50 W

    60W filament 60 W

    100W filament 100 W

    Emergency light/KELUAR sign 20 W

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    8/132

    Jun2002 ITiDi 8

    BEBAN-BEBAN KECIL

    Kipas siling/dinding 90 W

    Mata kipas siling 100 W

    Soket alir keluar 13A 250 W (domestik)

    300 W (industri)

    Soket alir keluar 15A 500 W

    Mata alat hawa dingin 1.2 kW (1.5h.p), 1.5 kW (2h.p),

    1.9kW (2.5h.p), 2.3kW (3h.p)

    Isolator 30A 2.3 kW

    Isolator 60A 3.7 kW

    Lain-lain Ikut arus kadaran

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    9/132

    Jun2002 ITiDi 9

    BEBAN LAMPU DISCHARGE

    Untuk anggaraan beban lampu discharge

    kadaran wattnya hendaklah didharab

    dengan faktur 1.8 untuk mengambil kira

    faktur kuasa lampu, kehilangan didalam

    cok atau ballast dan kesan harmonic

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    10/132

    Jun2002 ITiDi 10

    BEBAN-BEBAN BESAR

    Untuk beban besar nilai kuasa

    sebenarnya (kW/kVA), voltan bekalan,

    faktur kuasa dan kecekapannya

    hendaklah diketahui terlebih dahulu dantidak boleh menganggarnya begitu

    sahaja

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    11/132

    Jun2002 ITiDi 11

    TCL

    Total Connected Load (TCL) ialahjumlah beban anggaran (kW)

    dengan andaian kesemua beban-

    beban elektrik didalam sesuatupemasangan elektrik digunakan

    secara maksima dan serentak

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    12/132

    Jun2002 ITiDi 12

    FAKTUR KEPELBAGAIAN (DF)

    Ialah satu angka atau peratus yang

    menggambarkan kuasa tertinggi dari

    TCL yang digunakan serentak pada satu-

    satu masa tertentu Contohnya 100 buah lampu 100W yang

    dipasang hanya 80 buah sahaja di ON

    kan serentak pada satu-satu masa. Olehitu DF adalah 80% atau 0.8

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    13/132

    Jun2002 ITiDi 13

    KEHENDAK MAKSIMA (MD)

    MD ialah Beban Maksima (kW) yangdiperlukan oleh sesuatu pepasangantanpa mengira bila ianya akan berlaku.

    MD lazimnya adalah beban penuh danmungkin jugak lebih dari itu. Ialazimnya kurang atau paling tinggi samadengan TCL.

    MD = TCL x DF

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    14/132

    Jun2002 ITiDi 14

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    15/132

    Jun2002 ITiDi 15

    MENENTUKAN MD

    Dalam rekabentuk MD lazimnya tidak dapat

    ditentukan dengan tepat. Nilai MD hanyalah satu

    nilai anggaraan sahaja berdasarkan jadual atau

    pengalaman atau data-data tertentu. Namun bagiperekabentuk yang berpengalaman mereka boleh

    menentukan nilai MD yang lebih baik dan realistik

    walaupun tidak seratus peratus tepat. Nilai MD

    pula boleh berubah apabila pola penggunaanberubah. Nilai MD penting untuk menentukan

    kadaran pemutus litar utama

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    16/132

    Jun2002 ITiDi 16

    PERTAMBAHAN BEBAN

    Setelah MD dapat dianggarkan ia

    hendaklah ditambah 10% hingga 15%

    lagi untuk mengambil kira pertambahan

    beban dimasa akan datang. Jikaanggaran MD terlalu rendah mungkin

    pemutus litar tidak dapat menahan arus

    beban penuh, sebaliknya jika anggaraanMD terlalu tinggi pemasangan menjadi

    oversize, membazir dan tidak perlu

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    17/132

    Jun2002 ITiDi 17

    BEBAN ALAT HAWA DINGIN

    Jika pehak mekanikal lambat atau belumdapat menganggarkan beban alat hawa

    dingin mereka, formula berikut boleh

    digunakan, tetapi hanya untukketinggian siling standard 9 kaki:

    kW = 0.044615 x luas lantai (m)

    Beban sebenarnya hendaklah diperolehi

    dari pehak mekanikal

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    18/132

    Jun2002 ITiDi 18

    ESSENTIAL & NON-

    ESSENTIAL LOADS

    Essential Loads Loads that need supply atall times especially during normal supplyfailure such as corridor lights, computers,

    servers, PABX, security system, life supportequipment, operation room, etc.

    Non-Essential Loads Less important loadsthat do not require supply during normal supply

    failure such as normal office lightings, officeair cond system, etc

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    19/132

    Jun2002 ITiDi 19

    SUPPLY FOR ESSENTIAL

    LOADS

    Normally essential loads get immediate

    supply from UPS system

    (Uninterruptable Power Supply) for ashort duration and will be taken over by

    standby generator set after that.

    Different busbar shall be used to supply

    these loads and change over contactor

    shall be used

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    20/132

    Jun2002 ITiDi 20

    MENGIRA ARUS

    Gunakan formula:

    P (kW) = Vph x Iph x Cos (satu fasa)

    dan untuk tiga fasa:P (kW)= 3 x Vline x Iline x Cos

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    21/132

    Jun2002 ITiDi 21

    KEDUDUKAN LAMPU

    Bilangan lampu ditentukan menggunakanLumen Method atau cara lain yang sesuai.

    Kedudukan dan susunan lampu hendaklah

    sesuai dengan pencahayaan samarata dantidak bertindih dengan peralatan lain seperti

    grill air-cond, kipas siling dsb.

    Kedudukan suis hendaklah ditempat senang di

    akses dan tidak terlindung / terhalang.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    22/132

    Jun2002 ITiDi 22

    KEDUDUKAN MATA KUASA

    Didalam satu bilik mata kuasa hendaklahdari fasa yang sama, jika dua mata kuasa

    dari fasa yang berlainan jaraknya

    hendaklah tidak kurang dari 2 meter. Jarak dari pili air dan dapor hendaklah

    tidak kurang dari 2 meter.

    Tidak dibenarkan dipasang didalam bilikmandi kecuali untuk shaver unit.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    23/132

    Jun2002 ITiDi 23

    KEDUDUKAN MATA KUASA

    Soket outlet 13A yang TIDAK dipasangdidinding hendaklah menggunakan

    underfloor ducting/conduit/casing atau

    apa-apa cara yang sesuai dan diluluskan Cara ini diperlukan untuk bilik

    komputer, makmal, woksyop,

    supermarket dan sebagainya

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    24/132

    Jun2002 ITiDi 24

    SOKET BILIK KOMPUTER

    Bilik komputer selalunya memerlukanbilangan soket 13A yang banyak, oleh itu

    lebih baik dikhaskan satu DB untuknya.

    Penggunaan RCCB 30mA mungkinmenimbulkan masaalah disebabkan arus

    bocor yang tinggi, oleh itu RCCB 100mA

    boleh digunakan.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    25/132

    Jun2002 ITiDi 25

    LOKASI MSB, SSB, DB

    MSB hendaklah dekat dengan pusatbeban (load centre) untuk mengelakkan

    susut voltan yang melebehi 4%.

    SSB hendaklah digunakan jikasekumpulan beban berada agak jauh

    dari pusat beban untuk mejimatkan

    kabel dan memudahkan kawalan dansenggaraan.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    26/132

    Jun2002 ITiDi 26

    DISTRIBUTION BOARD (DB)

    Jika bilangan lampu dan soket 13Abanyak eloklah DB yang berasingandigunakan untuk memudahkan kerja-

    kerja senggaraan. Penggunaan RCCB tiga fasa tidak

    digalakkan disebabkan gangguan kepadafasa-fasa lain jika berlaku tripping.Gunakan tiga RCCB satu fasa untuk DBtiga fasa.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    27/132

    Jun2002 ITiDi 27

    PERINGKAT AGIHAN BEKALAN

    Bekalan dari TNB/Alatubah/Janakuasa

    Ke Papan Suis Utama (PSU/MSB)

    Ke Papan Suis Kecil (PSK/SSB)

    Ke DB atau beban besar

    Ke beban-beban melalui alat kawalan

    atau pensuisan

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    28/132

    Jun2002 ITiDi 28

    JENIS-JENIS PSU

    Tiada kompartmen

    Sebahagian sahaja berkompartmen

    Sepenuhnya berkompartmen

    Wall mounted

    Pedestal (floor mounted), front access

    Cubicle (front & back access) Cubicle (front access only)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    29/132

    Jun2002 ITiDi 29

    CUBICLE SWITCHBOARD

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    30/132

    Jun2002 ITiDi 30

    PEDESTAL

    SWITCHBOARD

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    31/132

    Jun2002 ITiDi 31

    WALLMOUNTED

    SWITCHBOARD

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    32/132

    Jun2002 ITiDi 32

    PEMILIHAN KABEL

    Jenis-Jenis Kabel:PVC, PVC/PVC, PVC/SWA/PVC

    PILC (Paper Insulated Lead Covered)

    PILCDSTAS ( Double Steel Tape &Amoured)

    XLPE (Cross Link Polyethylene)

    XLPE/SWA/PVC

    MICC (Mineral Insulated Copper Cable)FRC (Fire Rated cable)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    33/132

    Jun2002 ITiDi 33

    JENIS-JENIS PENDAWAIAN

    Permukaan (surface)

    Terbenam (consealed)

    Pembuluh permukaan (surface conduit)

    Pembuluh terbenam (consealed conduit) Sesalur (trunking)

    Ducting

    Dulang (tray)

    Riser/duct/trench

    Busduct/Ladder

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    34/132

    Jun2002 ITiDi 34

    PENDAWAIAN

    PERMUKAAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    35/132

    Jun2002 ITiDi 35

    PENDAWAIAN

    TERBENAM

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    36/132

    Jun2002 ITiDi 36

    PENDAWAIAN

    KONDUIT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    37/132

    Jun2002 ITiDi 37

    PENDAWAIAN TRUNKING DAN TRAY

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    38/132

    Jun2002 ITiDi 38

    SAIZ KABEL

    Kabel hendaklah cukup saiznya supaya:Boleh menanggung arus beban penuh

    dan arus pusuan (inrush current)

    Keupayaan membawa arusnyamelebehi dari keupayaan membawa

    arus pemutus litar yang mengawalnya

    Susut voltan tidak melebihi 4%

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    39/132

    Jun2002 ITiDi 39

    KABEL LITAR AKHIR

    Litar Fius/MCB Kabel (mm) Luas LantaiLampu &

    kipas

    5A/6A 1.5 -

    Litar gelang(soket 13A)

    30/32A 2.5 100m

    Litar radial

    soket 13A

    30/32A 4.0 50m

    Radial soket

    13A

    20A 2.5 20m

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    40/132

    Jun2002 ITiDi 40

    SAIZ KABEL PERLINDUNGAN

    Saiz kabel fasa (S) Saiz kabel perlindungan

    Kurang dari 16mm S

    16mm - 35mm 16mm

    Melebihi 35mm Separuh dari S

    Lebih dari 70mm

    pita tembaga 6mm x 25mm

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    41/132

    Jun2002 ITiDi 41

    KABEL PENGIKAT

    Kabel Pengikat (Bonding Conductor)hendaklah sama saiz dengan kabel

    perlindungan tetapi minima 4.0mm.

    Ia digunakan untuk menyambunganbahagian-bahagian logam berkonduktif

    dengan terminal bumi sepunya (common

    earthing terminal) untuk mengujudkanvoltan samaupaya.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    42/132

    Jun2002 ITiDi 42

    SAIZ KABEL-KABEL LAIN

    Ib

    In = ------------------------

    Ca + Cg + CiDimana : Ib = arus beban

    Ca = faktur suhu ambient

    Cg = faktur kumpulanCi = faktur penebat haba

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    43/132

    Jun2002 ITiDi 43

    SUSUT VOLTAN

    Vd = mV x I x L

    1000Vd - jumlah susut voltan (tak melebihi 4%)

    mV - susut voltan kabel (milivolt/A/m)

    I - arus beban (A)

    L - panjang kabel (meter)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    44/132

    Jun2002 ITiDi 44

    CARA CEPAT

    mV = 1000 x Vd

    A x L

    Dimana nilai Vd maksima

    ditetapkan dahulu

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    45/132

    Jun2002 ITiDi 45

    CONTOH

    Satu beban 18kW, 415V, p.f 0.85 berada90 meter dari MSB. Tentukan saiz kabel jenis PVC multicore tanpa perisai yangsesuai digunakan.

    I = 18,000/1.732x415x0.85 = 30A

    Dari jadual 4D1A, IEE 16, column 5 (3

    atau 4 kabel tertutup dlm. konduit atautrunking) saiz kabel yang sesuai ialah6mm

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    46/132

    Jun2002 ITiDi 46

    CONTOH

    Keupayaan membawa arus kabel 6mm

    ialah 36A, oleh itu ia mampu membawa arus

    tadi (30A)

    Tetapi nilai susut voltannya ialah 6.4

    milivolt/ampiar/meter (JADUAL 4D1B,

    column 6)

    Jumlah susut voltan Vd= 0.0064V x 30A x

    90m = 17.28V (melebihi 4% atau 16.6V), olehitu kabel 6mm tidak boleh digunakan

    CONTOH

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    47/132

    Jun2002 ITiDi 47

    CONTOH Oleh itu pilih saiz 10mm atau 16mm, tetapi cara

    ini lambat dan membuang masa Oleh itu gunakan cara cepat:

    mV = 1000 x (susut voltan maksima 16V) = 5.9mV

    30A x 90m

    Dari JADUAL 4D1B, column no 6, reference

    method 3 or 4, nilai mV yang diperolehi tadi berada

    diantara 6.4mV(6mm) dan 3.8mV(10mm) dan saiz

    yang boleh dipilih ialah 10mm sebab susutvoltannya kurang dari 5.9mV. Lebih besar saiz

    kabel maka lebih kuranglah susut voltannya

    SAIZ KONDUIT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    48/132

    Jun2002 ITiDi 48

    SAIZ KONDUIT

    Saiz konduit G.I atau PVC adalah terhad

    kepada maksima 32mm dan hanya boleh diisidengan kabel sebanyak 40% sahaja

    Jadual 12A memberikan faktur kabel untuk

    konduit tiada bengkok kurang dari 3 meter Jadual 12B memberikan faktur kabel untuk

    konduit untuk digunakan dengan Jadual 12A

    Jadual 12C memberikan faktur kabel untuk

    konduit melebehi 3 meter

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    49/132

    Jun2002 ITiDi 49

    SAIZ KONDUIT

    Gunakan appendix 12 IEE

    Jadual 12A

    Jadual 12B

    Jadual 12C

    Jadual 12E

    Jadual 12F

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    50/132

    Jun2002 ITiDi 50

    SAIZ-SAIZ KONDUIT

    STANDARD

    16mm

    20mm

    25mm

    32mm

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    51/132

    Jun2002 ITiDi 51

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    52/132

    Jun2002 ITiDi 52

    CONTOH

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    53/132

    Jun2002 ITiDi 53

    CONTOH

    Tentukan saiz konduit untuk memuatkan 9

    bilangan kabel PVC 1.5mm stranded,anggapkan konduit terdapat satu bengkokan

    (one bend)

    Dari Jadual 12A, kabel 1.5mm PVCfakturnya ialah 31, jumlah fakturnya

    ialah 9 x 31= 279, rujuk table 12D kita

    dapati angka yang paling hampir ialah294, oleh itu saiz konduit yang paling

    sesuai ialah 20mm

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    54/132

    Jun2002 ITiDi 54

    SAIZ-SAIZ TRUNKING

    (mm x mm)

    50 x 37.5 50 x 50

    75 x 50 75 x 75

    100 x 50 100 x 75 100 x 100

    150 x 50 150 x 75 150 x 75

    150 x 100 150 x 150

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    55/132

    Jun2002 ITiDi 55

    PAPAN AGIHAN

    Kabel masuk

    Pengasing/Suis Utama Berfius/MCB

    RCCB

    Palang bas hidup Fius/MCB

    Terminal Neutral

    Terminal bumi Numbering & Labelling

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    56/132

    Jun2002 ITiDi 56

    PAPAN AGIHAN SATU FASA

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    57/132

    Jun2002 ITiDi 57

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    58/132

    Jun2002 ITiDi 58

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    59/132

    Jun2002 ITiDi 59

    PAPAN

    AGIHAN

    TIGAFASA

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    60/132

    Jun2002 ITiDi 60

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    61/132

    Jun2002 ITiDi 61

    TYPICAL

    MAIN

    SWITCH

    BOARD

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    62/132

    Jun2002 ITiDi 62

    ONE INCOMING WITH GENSET

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    63/132

    Jun2002 ITiDi 63

    TWO INCOMING WITH GENSET

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    64/132

    Jun2002 ITiDi 64

    TYPICAL MAIN SWITCHBOARD WITH GENSET

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    65/132

    Jun2002 ITiDi 65

    BUSBAR SYSTEM

    Single busbar system

    Sectionalised single busbar system

    Sectionilised ring busbar system

    Duplicate busbar system

    KADARAN ARUS BUSBAR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    66/132

    Jun2002 ITiDi 66

    KADARAN ARUS BUSBAR

    Saiz Busbar (mm x mm) Kadaran Arus (A)

    6.3 x 40 4006.3 x 50 500

    6.3 x 63 600

    6.3 x 70 7006.3 x 80 800

    6.3 x 90 900

    6.3 x 100 10002 x 6.3 x 63 1200

    2 x 6.3 x 80 1600

    MINIMUM CLEARANCE INDOOR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    67/132

    Jun2002 ITiDi 67

    BUSBAR OPEN OR ENCLOSED

    Voltage (kV)

    Between Phase

    Min clearance to

    earth in air

    Min clearance to

    earth in air

    Min

    ClearanceBetweenphase in air

    Min

    ClearanceBetweenphase in air

    Open (in) Enclosed (in) Open (in) Enclosed (in)

    0.44 0.75 5/8 1.0 0.75

    0.66 1.0 0.75 1.25 1.02.2 1.5 1.5 1.5 1.5

    3.3 2.0 2.0 2.0 2.0

    6.6 2.5 2.5 3.5 3.511 3.0 3.0 5.0 5.0

    22 5.5 5.5 9.5 9.5

    33 8.75 8.75 14 14

    MINIMUM CLEARANCE OUTDOOR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    68/132

    Jun2002 ITiDi 68

    MINIMUM CLEARANCE OUTDOOR

    BUSBAR OPEN TYPE

    Voltage (kV)

    Between Phase

    Min clearance to

    earth in air (in)

    Min clearance

    bet. phase in air

    6.6 6 8

    11 7 11

    22 9 17

    33 13 23

    MINIMUM CLEARANCE BETWEEN BUSBAR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    69/132

    Jun2002 ITiDi 69

    MINIMUM CLEARANCE BETWEEN BUSBAR

    IMMERSED IN COMPOUND OR OIL

    Voltage (kV)

    Between Phase

    Min clearance to

    earth (in)

    Min clearance

    bet. phase (in)

    0.66 0.5 0.75

    3.3 0.5 0.75

    6.6 0.75 1.0

    11 1.0 1.5

    22 1.75 2.5

    33 2.5 3.5

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    70/132

    Jun2002 ITiDi 70

    MELTING POINT OF COPPER

    Melting point of copper is at 1,084 degrees

    C

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    71/132

    Jun2002 ITiDi 71

    COPPER VS ALUMINIUM

    CU AL

    Weight for equal conductivity 1.0 0.5

    Conductivity for equal areas 1.0 0.61

    Tensile strength (hard drawn) 1.0 0.4

    Hardness (hard drawn) 1.0 0.44

    Modulus of elasticity 1.0 0.55

    Co-efficient of thermal expansion 1.0 1.39

    Melting point 1.0 0.61

    SISTEM PERLINDUNGAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    72/132

    Jun2002 ITiDi 72

    SISTEM PERLINDUNGAN

    Overcurrent (O/C)/Litar pintas

    Overload

    Earth Leakage (arus bocor kebumi)

    Earth Fault (rosak ke bumi)

    Lightning

    Surge

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    73/132

    Jun2002 ITiDi 73

    ALAT PERLINDUNGAN

    Fius (fius suis, suis fius) MCB (miniature c.b)

    MCCB (moulded case c.b)

    ACB (air circuit breaker)

    RCCB (residual current c.b)

    Current Transformer (C.T)

    Relay

    SPD (surge protection device)

    PEMILIHAN ALAT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    74/132

    Jun2002 ITiDi 74

    PEMILIHAN ALAT

    PERLINDUNGAN

    Arus kadaran (current rating)

    kA rating

    Harga

    Mudah disenggara

    Trend terkini

    Praktikaliti/Kesesuaian Technical performance

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    75/132

    Jun2002 ITiDi 75

    FAKTUR FIUS

    Ialah arus minima yang akan meleburkan

    elemen fius dibahagikan dengan arus

    kadaran fius. Fius dawai - 2

    Fius katrij - 1.5

    Fius HRC - 1.25 ke 1.5

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    76/132

    Jun2002 ITiDi 76

    KADARAN FIUS SUIS

    100A

    160A

    250A

    300A

    400A

    600A

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    77/132

    Jun2002 ITiDi 77

    KADARAN MCB

    6A

    10A

    15A

    20A

    32A

    KADARAN MCCB

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    78/132

    Jun2002 ITiDi 78

    KADARAN MCCB

    30A 300A

    60A 400A

    100A 500A

    125A 600A

    150A 800A

    200A 1000A 250A 1200A

    KADARAN ACB

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    79/132

    Jun2002 ITiDi 79

    KADARAN ACB

    600A 3000A

    800A 3500A

    1000A 4500A

    1250A 6300A

    1600A

    2000A 2500A

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    80/132

    Jun2002 ITiDi 80

    BUS TIE/BUS COUPLER

    Jika sesuatu pemasangan itu mendapat dua

    atau lebih punca bekalan TNB kedua-dua

    nya boleh dihubungkan menggunakan bus

    tie/bus coupler dan hendaklah dari jenisempat kutub. Sistem ini hendaklah dipasang

    dengan castle key untuk mengelakkan

    kedua-dua bekalan dari bertembung tanpasynchronising dibuat terlebih dahulu

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    81/132

    Jun2002 ITiDi 81

    CHANGE OVER CONTACTOR

    Jika sesuatu pemasangan perlu

    mempunyai janakuasa tunggusedia

    bekalannya hendaklah disambungkan

    kepada MSB menggunakan change overcontactor (C.O.C) untuk operasi secara

    otomatik dan hendaklah dari jenis empat

    kutub

    DISKRIMINASI

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    82/132

    Jun2002 ITiDi 82

    DISKRIMINASI

    Menentukan tahap arus atau arus &masa disetiap bahagian litar supaya jika

    berlaku gangguan bekalan akan

    melibatkan hanya bahagian yang kecildan tidak melibatkan bahagian-bahagian

    lain yang tidak berkaitan.

    DISKRIMINASI

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    83/132

    Jun2002 ITiDi 83

    DISKRIMINASI

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    84/132

    Jun2002 ITiDi 84

    DISKRIMINASI

    FAULT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    85/132

    Jun2002 ITiDi 85

    DISKRIMINASIARUS & MASA

    PERLINDUNGAN LITAR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    86/132

    Jun2002 ITiDi 86

    PERLINDUNGAN LITAR

    AKHIR Untuk perlindungan arus lebih/ beban

    lebih - menggunakan fius berkadaran 5A,

    10A, 15A, 20A,30A, 63A atau MCBberkadaran 6A, 10A, 15A, 20A, 32A, 60A

    Untuk perlindungan bocor ke bumi

    menggunakan RCCB berkepekaan 30mAatau 100mA

    PERLINDUNGAN LITAR AKHIR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    87/132

    Jun2002 ITiDi 87

    PERLINDUNGAN LITAR AKHIR

    Fius/MCB Kabel Had Kuasa

    5/6A 1.5mm 10 mata lampu/kipas, TCL maksima 1000/1200W15A 2.5mm 1 bil s/s/o 13A

    20A 2.5mm 2 bil s/s/o 13A

    30A (ring) 2.5mm 10/Tiada had tetapi dalam ruang 100m persegi

    30A (radial) 4.0mm 6 bil s/s/o 13A15A 2.5mm 1 bil cooker unit < 3kW

    15A 4.0mm 1 bil s/o 15A

    15A 4.0mm 1 bil 1.5kW water heater

    15A 4.0mm 1 bil 1.5h.p penghawa dingin30A 6.0mm 1 bil 2.5h.p penghawa dingin

    30A 6.0mm 1 bil 3.0h.p penghawa dingin

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    88/132

    Jun2002 ITiDi 88

    TINGKAT

    BAWAH

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    89/132

    Jun2002 ITiDi 89

    TINGKAT

    SATU

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    90/132

    Jun2002 ITiDi 90

    TINGKAT

    DUA

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    91/132

    Jun2002 ITiDi 91

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    92/132

    Jun2002 ITiDi 92

    KIRAAN BEBAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    93/132

    Jun2002 ITiDi 93

    Item Qty TCL DF MD (kW)

    1x40W(F) 3 3x50W 100% 0.152x40W (F) 14 14x50W 100% 0.7

    Exhaust fan 6 6x90W 100% 0.54

    Soket 13A 9 9x250W 80% 1.8

    Air cond 1hp 1 1x1.2kW 100% 1.2

    Air cond 2hp 2 2x1.5kW 100% 3.0

    Air cond 2.5hp 2 2x1.9kW 100% 3.8

    JUMLAH 11.18kW

    KIRAAN BEBAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    94/132

    Jun2002 ITiDi 94

    KIRAAN BEBAN

    Jumlah MD = 11.18kW

    Arus beban penuh (I):

    I = 11,180W 240V = 46.58A

    BILANGAN HALA PAPAN AGIHAN

    No Kadaran Beban Kabel

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    95/132

    Jun2002 ITiDi 95

    Litar Fius/MCB (mm)

    1 6A 7nos 2x40W(F) + 3nos 1x40W(F) 1.5

    2 6A 7nos 2x40W(F) 1.5

    3 6A 6 nos exhaust fan 1.5

    4 6A spare

    5 6A spare

    6 32A(ring cct.) 5nos 13A s/s/o 2.5

    7 32A(ring cct.) 4nos 13A s/s/o 2.5

    8 32A spare

    9 32A spare

    10 20A 1no 1.0hp air cond point 4.0

    11 20A 1no 2.0hp air cond point 4.0

    12 20A 1no 2.0hp air cond point 4.0

    13 32A 1no 2.5hp air cond point 6.014 32A 2no 2.5hp air cond point 6.0

    15 32A spare

    16 32A spare

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    96/132

    Jun2002 ITiDi 96

    AGIHAN

    BEBAN

    SEIMBANG

    ANTARA

    FASA

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    97/132

    Jun2002 ITiDi 97

    PERLINDUNGAN SUB MAIN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    98/132

    Jun2002 ITiDi 98

    PERLINDUNGAN SUB MAIN

    Menggunakan Fius Suis (F/S) atauMCCB dengan geganti ELR dan

    alatubah arus Z

    Menggunakan ACB jika beban sub mainadalah besar

    Menggunakan Oil Dash Pot relay

    E/F relay jenis IDMT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    99/132

    Jun2002 ITiDi 99

    OIL

    DASH

    POT

    RELAY

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    100/132

    Jun2002 ITiDi 100

    EARTH

    LEAKAGE

    RELAY

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    101/132

    Jun2002 ITiDi 101

    IDMT

    RELAY

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    102/132

    Jun2002 ITiDi 102

    IDMT

    RELAY

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    103/132

    Jun2002 ITiDi 103

    EARTH

    FAULT

    RELAY

    PERLINDUNGAN SOLID

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    104/132

    Jun2002 ITiDi 104

    EARTHING

    Perlindungan earth leakage/earth faulttanpa menggunakan geganti , ELCB atau

    RCCB

    Hanya menggunakan fius atau MCB

    Sistem pembumian mestilah baik

    Rintangan elektrod bumi mestilah

    serendah mungkin

    Untuk saiz pemasangan yang kecil

    RCCB/ELCB

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    105/132

    Jun2002 ITiDi 105

    RCCB/ELCB

    13A, 2 kutub, 10mA untuk alatpermainan kanak-kanak.

    40A/43A, 2 kutub, 30mA untuk litarsoket alir keluar 13A secara individuatau berkumpulan.

    60A/63A, 2 kutub, 100mA untuk DB satufasa lampu, kipas dan soket alir keluar.

    60A/63A, 4 kutub, 300mA.

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    106/132

    Jun2002 ITiDi 106

    RCCB

    PERLINDUNGAN KILAT

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    107/132

    Jun2002 ITiDi 107

    PERLINDUNGAN KILAT

    Bangunan melebihi 2 tingkat atau Bangunan ditempat tinggi atau

    Bangunan dikawasan lapang seperti

    sawah padi Air finial, horizontal conductor, down

    conductor, inspection point, earthchamber, earth electrode. Copper tape,

    Aluminium tape or G.I wire.

    ARUS/VOLTAN PUSUAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    108/132

    Jun2002 ITiDi 108

    ARUS/VOLTAN PUSUAN

    Apabila berlaku arus/voltan pusuan(current/voltage surge) peralatan mudah

    rosak

    Surge suppressor Lightning arrester

    Surge diverter

    LUKISAN ELEKTRIK

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    109/132

    Jun2002 ITiDi 109

    LUKISAN ELEKTRIK

    Standard symbol Schematic diagram

    Workshop drawing

    Wiring diagram

    Layout diagram

    Key plan/Site plan

    KOD WARNA

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    110/132

    Jun2002 ITiDi 110

    KOD WARNA Merah untuk fasa merah atau wayer

    hidup

    Kuning untuk fasa kuning

    Biru untuk fasa biru

    Hitam untuk neutral (tiga fasa)

    Coklat untuk wayer hidup (satu fasa)

    Biru untuk wayer neutral (satu fasa) Hijau / hijau berjalur kuning untuk bumi

    KETINGGIAN PERALATAN

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    111/132

    Jun2002 ITiDi 111

    Peralatan tergantung di siling 240cm (8ka)Peralatan terlekat di dinding 205cm (6ka 9in)

    Suis lampu/kipas 145cm (4ka 9in)

    Soket alir keluar 145cm (4ka 9in)

    Soket alir keluar 30cm (1ka)

    Papan agihan 205cm (6ka 9in)

    BILL OF QUANTITIES (B.Q)

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    112/132

    Jun2002 ITiDi 112

    BILL OF QUANTITIES (B.Q)

    Untuk memudahkan membuat anggarandan menyemak perubahan serta

    penambahan/pengurangan kuantiti

    Memudahkan pemborong membuatsebutharga kerja

    Mengelakkan keraguan daripada

    perkara yang kurang jelas

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    113/132

    Jun2002 ITiDi 113

    B.Q

    POWER FACTOR CAPACITOR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    114/132

    Jun2002 ITiDi 114

    POWER FACTOR CAPACITOR

    BANK

    Power Factor Capacitor Bank perlu

    dipasang untuk mempastikan faktur

    kuasa pemasangan tidak rendahdaripada 0.85 kerana jika rendah

    daripada itu pehak TNB akan

    mengenakan denda kepada pengguna

    yang terlibat

    TARIFF ELEKTRIK

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    115/132

    Jun2002 ITiDi 115

    Caj kemasukan bekalan Sumbangan perkhidmatan

    Cagaran

    kWh (unit) digunakan

    kW permintaan maksima (tarif C1)

    Caj faktur kuasa rendah dari 0.85

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    116/132

    Jun2002 ITiDi 116

    SOALAN

    Berdasarkan lukisan yang diberikan

    dapatkan TCL dan MD sertakan lakarkan

    rajah skema SSB bangunan tersebut lengkapdengan saiz kabel, saiz busbar, kadaran arus

    pemutus litar incoming dan outgoing serta,

    nisbah c.t dan julat (range) alat-alat

    pengukuran

    SENARAI BEBAN SSB

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    117/132

    Jun2002 ITiDi 117

    Lokasi/Beban MD MCCB

    1. Ground floor 19kW 63A

    2. First floor 25kW 63A

    3. Second floor 13kW 63A

    4. Third floor 13kW 63A

    5. Air cond central unit 50kW 200A

    6. Water pump 5kW 63A

    7. Fire fighting pump 5kW 63A

    8. Compound lighting 4kW 63A

    SENARAI BEBAN UNTUK MSB

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    118/132

    Jun2002 ITiDi 118

    Bangunan/Beban MD Jarak

    1. Blok pentadbiran 120kW 90m

    2. Bangunan akan datang 120kW 130m

    3. Bengkel 100kW 210m

    4. Dewan akan datang 150kW 120m

    5. Kantin 8kW 180m

    6. Surau 4kW 230m

    7. Pam air 5kW 70m

    8. Lampu kawasan 4kW 90m

    MCCB & SAIZ KABEL

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    119/132

    Jun2002 ITiDi 119

    Beban Arus MCCB Kabel V.Drop1. 120kW 196A 250A 120mm o.k

    2. 120kW 196A 250A 120mm o.k

    3. 100kW 164A 200A 70mm 95mm4. 150kW 246A 300A 150mm o.k

    5. 8kW 14A 63A 16mm o.k

    6. 4kW 6.5A 30A 10mm o.k

    7. 5kW 8A 30A 10mm o.k

    8. 3kW 5A 30A 10mm o.k

    KADARAN ACB & BUSBAR

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    120/132

    Jun2002 ITiDi 120

    KADARAN ACB & BUSBAR

    Jumlah MD = 510kW

    I = 835A

    Kadaran ACB = 1250A Saiz busbar : 4 x 2 x 6.3mm x 63mm

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    121/132

    Jun2002 ITiDi 121

    QUESTION

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    122/132

    Jun2002 ITiDi 122

    A 4 core PVC/SWA/PVC copper cable is to be

    installed from SSB A to a 3 phas 415V motorwith a full load current of 102A and a p.f of0.75lagging, along with two similar fixed to aperforated cable tray, where sheaths would be

    touching. Circuit is to be protected by a BSHRC fuse. Cable is 100m, ambient temp. 30 degC, voltage drop from MSB up to SSB A is 9V.

    Determine the normal rating of the fuse, size ofcable if total voltage drop from MSB to load isnot to exceed 4%

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    123/132

    Jun2002 ITiDi 123

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    124/132

    Jun2002 ITiDi 124

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    125/132

    Jun2002 ITiDi 125

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    126/132

    Jun2002 ITiDi 126

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    127/132

    Jun2002 ITiDi 127

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    128/132

    Jun2002 ITiDi 128

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    129/132

    Jun2002 ITiDi 129

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    130/132

    Jun2002 ITiDi 130

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    131/132

    Jun2002 ITiDi 131

  • 8/2/2019 f307139672_REKABENTUK_ELEKTRIK

    132/132